Creation of the data models in the Jupyter Notebook twe_flex_data_modell.ipynb
-
JSON schema files schemes for the relevant entities
-
The data model is based on NGSI-v2 and the VDI 3814 - 4.1
- The ID of Entities is generated from the entity type and an ID, such as
entity-type:ID
- The ID of the attribute is given by a combination of
- the following parts:
- Subcomponent (Part of the entity)
- Type of data point
- Position of the data point
- with the following strucur:
subcomponent__data-point-type__data-point-position
- the following parts:
- The ID of Entities is generated from the entity type and an ID, such as
-
An overview of the data points is provided in the following table
Entity-Type | Example Entity ID | Description | Attribute ID | Attribute Type | Data Type | Unit | Description |
---|---|---|---|---|---|---|---|
thermal_storage |
thermal_storage:001 |
Thermal Storage | hw__temperature__20 |
attribute | Number | °C | Temperature of the heating water in position at 20 per cent of the high of the thermal storage tank |
hw__temperature__50 |
attribute | Number | °C | Temperature of the heating water in position at 50 per cent of the high of the thermal storage tank | |||
hw__temperature__80 |
attribute | Number | °C | Temperature of the heating water in position at 50 per cent of the high of the thermal storage tank | |||
hw__temperature__x |
attribute | Number | °C | Temperature at point x (numbering/height in %) (if more points are needed) | |||
hw__volume |
static_attribute | Number | m³ | Volume of heating water in storage | |||
dhw_installation |
dhw_installation:001 |
Domestic Hot Water Installation | dhw__temperature__in |
attribute | Number | °C | Inlet temperature of DHW |
dhw__temperature__out |
attribute | Number | °C | Outlet temperature of DHW | |||
dhw__temperature__x |
attribute | Number | °C | DHW temperature at a specific position | |||
dhw__volumeflow |
attribute | Number | m³/h | Volume flow of DHW in the pipe | |||
dhw_installation |
dhw_measuring_section:001 |
DHW Measuring Section Laboratory | dhw__status__volumeflow |
attribute | Number | - | Status of which flow meter is used |
tmb__temperature__x |
attribute | Number | °C | Temperature of the heat tape | |||
ambient__temperature__x |
attribute | Number | °C | Ambient temperature | |||
dhw_installation |
dhw_distribution:001 |
DHW Distribution Laboratory | dhw__temperature__setpoint |
attribute | Number | °C | Setpoint temperature measurement |
dhw__temperature__setpoint |
command | Number | °C | Setpoint temperature for DHW | |||
dhw__status__measuring_section |
attribute | Number | - | Status if the measuring section is flowing | |||
dhw__status__bypass |
attribute | Number | - | Status if the bypass is flowing | |||
dhw__volumeflow__setpoint |
attribute | Number | m³/h | l/min | |||
dhw__volumeflow__setpoint |
command | Number | m³/h | l/min | |||
dhw_installation |
dhw_calculation:001 |
Calculated Values for DHW | dhw__temperature__mean |
attribute | Number | °C | Calculated temperature of DHW |
dhw__tapping |
attribute | Number | - | Detection of tapping events | |||
calculation__time__temperature |
attribute | Number | SEC | Calculation time for temperature | |||
calculation__time__tapping |
attribute | Number | SEC | Calculation time for tapping detection | |||
temperature_maintenance_band |
temperature_maintenance_band:001 |
temperature maintenance band / pipe heating system | electrical_input__resistance |
attribute | Number | Ohm | Resistance of the heat tape |
electrical_input__voltage |
attribute | Number | V | Voltage of the heat tape | |||
electrical_input__current |
attribute | Number | A | Current of the heat tape | |||
electrical_input__power |
attribute | Number | W | Power of the heat tape | |||
electrical_input__energy |
attribute | Number | Wh | Energy consumption of the heat tape | |||
operation__status |
attribute | Number | - | Operating status of the heat tape | |||
operation__status |
command | Number | - | Operating status of the heat tape | |||
operation__error |
attribute | Number | - | Error code | |||
operation__warning |
attribute | Number | - | Warning code | |||
operation__duty_cycle__lenght |
attribute | Number | s | Length of the duty cycle | |||
operation__duty_cycle__active |
attribute | Number | % | Active part of the duty cycle | |||
operation__duty_cycle__active |
command | Number | % | Active part of the duty cycle | |||
calculation_coefficient__length |
static_attribute | Number | m | Length of the heat tape | |||
calculation_coefficient__resistance |
static_attribute | StructuredValue | - | Coefficients for calculation from resistance to temperature | |||
calculation_coefficient__temperature |
static_attribute | StructuredValue | - | Coefficients for calculation from temperature to DHW temperature | |||
dhw__temperature |
attribute | Number | °C | Measurement point for DHW temperature | |||
heat_meter |
heat_meter:001 |
Heat Meter | heat__temperature__in |
attribute | Number | °C | Inlet temperature |
heat__temperature__out |
attribute | Number | °C | Outlet temperature | |||
heat__volumeflow |
attribute | Number | m³/h or l/min | Volume flow | |||
heat__power |
attribute | Number | W or kW | Heat power | |||
heat__energy |
attribute | Number | kWh | MWh | |||
heat_transfer_station |
heat_transfer_station:001 |
Heat Transfer Station | operation__mode |
command | String / StructuredValue | - | Operating mode of the heat transfer station |
heat__power__rated |
static_attribute | Number | W or kW | Rated power in the reference case | |||
heat__power__setpoint |
command | Number / StructuredValue | W or kW | Setpoint power in the reference case | |||
heat__temperature__setpoint |
command | Number / StructuredValue | °C | Setpoint temperature in the reference case | |||
heat__meter__in |
Relationship | heat_meter | - | Heat meter for the reference case | |||
dhw_station |
dhw_station:001 |
DHW Station | dhw__temperature__setpoint |
command | Number / StructuredValue | °C | Setpoint temperature for the dhw |
heat__meter__in |
Relationship | heat_meter | - | Heat meter for the reference case |
-
EnOB: TWE-Flex - Optimisation and flexibilisation of domestic hot water heating systems
Project Website
We gratefully acknowledge the financial support of the Federal Ministry
for Economic Affairs and Climate Action (BMWK), promotional reference 03EN1056A-B.