Merge pull request #1983 from ibpsa/issue1982_movingAverage
Browse files Browse the repository at this point in the history
replaced moveing average
  • Loading branch information
mwetter authored Mar 6, 2025
2 parents 4d22bdf + c58e142 commit b43e77d
Show file tree
Hide file tree
Showing 3 changed files with 20 additions and 384 deletions.
201 changes: 9 additions & 192 deletions IBPSA/ThermalZones/ISO13790/Validation/BESTEST/Cases6xx/Case600.mo
Original file line number Diff line number Diff line change
Expand Up @@ -93,10 +93,10 @@ model Case600
u(unit="W"),
y(unit="J", displayUnit="J")) "Cooling energy in Joules"
annotation (Placement(transformation(extent={{54,74},{66,86}})));
MovingAverage PHea(delta=3600)
IBPSA.Controls.OBC.CDL.Reals.MovingAverage PHea(delta=3600)
"Hourly averaged heating power"
annotation (Placement(transformation(extent={{34,84},{42,92}})));
MovingAverage PCoo(delta=3600) "Hourly averaged cooling power"
IBPSA.Controls.OBC.CDL.Reals.MovingAverage PCoo(delta=3600) "Hourly averaged cooling power"
annotation (Placement(transformation(extent={{38,22},{46,30}})));

Modelica.Blocks.Sources.CombiTimeTable TSetCoo(table=[0.0,273.15 + 27])
Expand All @@ -107,196 +107,6 @@ model Case600
Modelica.Blocks.Sources.Constant latGai(k=0) "Internal heat gains"
annotation (Placement(transformation(extent={{-80,-60},{-60,-40}})));

protected

block MovingAverage "Block to output moving average"
parameter Real delta(
final quantity="Time",
final unit="s",
min=1E-5)
"Time horizon over which the input is averaged";
Modelica.Blocks.Interfaces.RealInput u
"Connector of Real input signal"
annotation (Placement(transformation(extent={{-140,-20},{-100,20}})));
Modelica.Blocks.Interfaces.RealOutput y
"Connector of Real output signal"
annotation (Placement(transformation(extent={{100,-20},{140,20}})));

protected
parameter Real tStart(
final quantity="Time",
final unit="s",
fixed=false)
"Start time";
Real mu
"Internal integrator variable";
Real muDel
"Internal integrator variable with delay";
Boolean mode(
start=false,
fixed=true)
"Calculation mode";

initial equation
tStart=time;
mu=0;

equation
u=der(mu);
muDel=delay(
mu,
delta);
// Compute the mode so that Dymola generates
// time and not state events as it would with
// an if-then construct
when time >= tStart+delta then
mode=true;
end when;
if mode then
y=(mu-muDel)/delta;
else
y=(mu-muDel)/(time-tStart+1E-3);
end if;
annotation (
defaultComponentName="movAve",
Icon(
graphics={
Rectangle(
extent={{-100,-100},{100,100}},
lineColor={0,0,127},
fillColor={255,255,255},
fillPattern=FillPattern.Solid),
Polygon(
points={{-78,90},{-86,68},{-70,68},{-78,90}},
lineColor={192,192,192},
fillColor={192,192,192},
fillPattern=FillPattern.Solid),
Line(
points={{-78,68},{-78,-80}},
color={192,192,192}),
Line(
points={{-88,0},{70,0}},
color={192,192,192}),
Polygon(
points={{92,0},{70,8},{70,-8},{92,0}},
lineColor={192,192,192},
fillColor={192,192,192},
fillPattern=FillPattern.Solid),
Line(
points={{-78,-31},{-64,-31},{-64,-15},{-56,-15},{-56,-63},{-48,-63},
{-48,-41},{-40,-41},{-40,43},{-32,43},{-32,11},{-32,11},{-32,-49},
{-22,-49},{-22,-31},{-12,-31},{-12,-59},{-2,-59},{-2,23},{4,23},
{4,37},{10,37},{10,-19},{20,-19},{20,-7},{26,-7},{26,-37},
{36,-37},{36,35},{46,35},{46,1},{54,1},{54,-65},{64,-65}},
color={215,215,215}),
Line(
points={{-78,-24},{68,-24}}),
Text(
extent={{-140,152},{160,112}},
textString="%name",
textColor={0,0,255}),
Text(
extent={{-42,-63},{41,-106}},
textColor={192,192,192},
textString="%delta s"),
Text(
extent={{226,60},{106,10}},
textColor={0,0,0},
textString=DynamicSelect("",String(y,
leftJustified=false,
significantDigits=3)))}),
Documentation(
info="<html>
<p>
This block outputs the mean value of its input signal as
</p>
<pre>
1 t
y = - &int; u(s) ds
&delta; t-&delta;
</pre>
<p>
where <i>&delta;</i> is a parameter that determines the time window over
which the input is averaged.
For
<i> t &lt; &delta;</i> seconds, it outputs
</P>
<pre>
1 t
y = -------- &int; u(s) ds
t-t<sub>0</sub>+10<sup>-10</sup> t<sub>0</sub>
</pre>
<p>
where <i>t<sub>0</sub></i> is the initial time.
</p>
<p>
This block can for example be used to output the moving
average of a noisy measurement signal.
</p>
<p>
See
<a href=\"modelica://IBPSA.Controls.OBC.CDL.Continuous.Validation.MovingAverage\">
IBPSA.Controls.OBC.CDL.Continuous.Validation.MovingAverage</a>
and
<a href=\"modelica://IBPSA.Controls.OBC.CDL.Continuous.Validation.MovingAverage_nonZeroStart\">
IBPSA.Controls.OBC.CDL.Continuous.Validation.MovingAverage_nonZeroStart</a>
for example.
</p>
</html>",
revisions="<html>
<ul>
<li>
January 27, 2022, by Jianjun Hu:<br/>
Renamed the block name from MovingMean to MovingAverage.<br/>
This is for <a href=\"https://github.com/lbl-srg/modelica-buildings/issues/2865\">issue 2865</a>.
</li>
<li>
November 12, 2020, by Michael Wetter:<br/>
Reformulated to remove dependency to <code>Modelica.Units.SI</code>.<br/>
This is for
<a href=\"https://github.com/lbl-srg/modelica-buildings/issues/2243\">issue 2243</a>.
</li>
<li>
March 2, 2020, by Michael Wetter:<br/>
Changed icon to display dynamically the output value.
</li>
<li>
October 24, 2017, by Michael Wetter:<br/>
Set initial condition for <code>mu</code>.
</li>
<li>
October 17, 2017, by Michael Wetter:<br/>
Reformulated implementation to avoid direct feedthrough.
</li>
<li>
October 16, 2017, by Michael Wetter:<br/>
Reformulated implementation to handle division by zero as the previous
implementation caused division by zero in the VAV reheat model with the Radau solver.
</li>
<li>
September 27, 2017, by Thierry S. Nouidui:<br/>
Reformulated implementation to handle division by zero.
This is for
<a href=\"https://github.com/lbl-srg/modelica-buildings/issues/978\">issue 978</a>.
</li>
<li>
September 15, 2017, by Thierry S. Nouidui:<br/>
Reformulated implementation to avoid state events.
</li>
<li>
July 5, 2017, by Michael Wetter:<br/>
Revised implementation to allow non-zero start time.
</li>
<li>
June 29, 2017, by Jianjun Hu:<br/>
First implementation. This is for
<a href=\"https://github.com/lbl-srg/modelica-buildings/issues/825\">issue 825</a>.
</li>
</ul>
</html>"));
end MovingAverage;


equation
connect(sumHeaCoo.y,preHeaCoo. Q_flow)
annotation (Line(points={{62.4,60},{68,60}}, color={0,0,127}));
Expand Down Expand Up @@ -355,6 +165,13 @@ for heating and <i>27</i>&deg;C for cooling. The room has no shade and a window
</p>
</html>", revisions="<html><ul>
<li>
March 5, 2025, by Jianjun Hu:<br/>
Replaced the moving average calculation with CDL block.
This is for
<a href=\"https://github.com/ibpsa/modelica-ibpsa/issues/1982\">
IBPSA #1982</a>.
</li>
<li>
May 2, 2024, by Alessandro Maccarini:<br/>
Updated according to ASHRAE 140-2020.
</li>
Expand Down